Schneider Altivar Process ATV660 · 1 to 125 HP · 208, 230, 460 V

← All A&C tools
Need an open (panel-mount) drive instead? Use the VFD Selector. This tool builds the Schneider ATV660 Process Drive catalog number (enclosed ATV630, 1–125 HP normal duty).

Already have an ATV660 number? Decode it

Paste a number from a quote. The tool explains each code and loads it into the form below so you can change it.

Or build one: 1. Motor and drive

Normal: pumps and fans (110% for 60 s). Heavy: conveyors, mixers, high starting torque (150% for 60 s).
Checked against the drive's rated amps.

2. Enclosure and power circuit

Type 1 indoor. Type 12 dusty or dripping. Type 3R outdoor.
Bypass runs the motor across the line if the drive fails.

3. Door controls and pilot lights

The keypad is always on the door.

4. Communication and options

Modbus and Ethernet (Modbus TCP) are built into the drive. Pick a card only for another network.

Wiring, power and enclosure

Drive cards and signals

Contacts, meters and timers EP = engineered option

More options the A&C Team adds in Schneider's Selector no code in the part number

These have no published letter code. Check any you need. They go on the parts list and email as a request, and the A&C Team adds them when they build the quote.

5. Your enclosed drive

Parts list

Ratings table NHA91297 Table 7, normal duty

Rated amps without bypass = drive output current. With bypass, Schneider's quote shows the lower bypass current as the maximum output amps. Heavy duty uses the next larger drive; its rated amps are those of the horsepower you picked.

What comes standard and items to confirm
  • Every drive: door-mounted circuit breaker disconnect, 100 kA SCCR, 3% line impedance, door-mounted keypad, built-in Modbus and Ethernet.
  • With bypass: Drive-Off-Bypass and Test-Normal switches, bypass overload relay with door reset, IEC bypass contactors, one Form C each for run, trip and bypass-run.
  • Type 3R ships service-entrance rated (no extra code). Service entrance is not available with the cUL label. Keep a 3R drive energized to prevent condensation.
  • Paint: Schneider's Selector printed RAL 7035 light gray on a configured quote, but ANSI 49 when the number was pasted in. Confirm the color on the quote if it matters.
  • EP options are engineered to order. Schneider's quote says standard lead times no longer apply and the enclosure size may change.
  • Soft-start bypass: the soft starter (ATS22 or ATS480) is chosen in Schneider's Selector. Confirm with the A&C Team.
  • Above 125 HP (ATVG60 inside, to 900 HP) is coming to this tool later. Call the A&C Team.